Parameter
Item
No.
Switch setting
0407
Error time
0403
output mode
H/W error
time PLC
4004
operation
mode
Detailed
setting
I/O response
0405
time
*1
0406
Control PLC
*1: Not available for the Redundant CPU.
(11)Acknowledge XY assignment
The parameters set in the I/O assignment, Ethernet/CC IE/MELSECNET setting, and CC-Link setting can be
confirmed.
Parameter
Item
No.
X/Y assignment
-
Table8.9 I/O assignment setting list (continued)
Description
Set various switches of an
H
intelligent function module.
Set whether to clear or hold the
output in case of a stop error in
H
the control CPU.
Set whether to stop or continue
the operation of the control
CPU in case of a hardware
H
failure of the intelligent function
module.
Set a response time for the
input module, high-speed input
H
module, I/O combined module,
or interrupt module.
Set the control CPU for the input/
output modules and intelligent
H
function module.
Figure 8.22 Acknowledge XY assignment
Table8.22 Acknowledge X/Y assignment list
Description
The data set in the I/O assignment, Ethernet/CC IE/
MELSECNET setting, and CC-Link setting can be
checked.
Setting range
Refer to the manual for the
Blank
intelligent function module used.
Clear/Hold
Clear
Stop/Continue
Stop
• Input or I/O mix: 1ms, 5ms,
10ms, 20ms, or 70ms
• Hi input or Interrupt: 0.1ms,
0.2ms, 0.4ms, 0.6ms, or 1ms
No.1, No.2, No.3, or No.4
No.1
Setting range
-
CHAPTER8 PARAMETERS
Default
Reference
Section 6.10
Section 6.8
Section 6.9
• Input or I/O mix:
10ms
Section 6.7
• Hi input or Interrupt:
0.2ms
QCPU User's
Manual (Multiple
CPU System)
Default
Reference
-
-
8 - 24
1
2
3
4
5
6
7
8