Mitsubishi 00JCPU User Manual page 446

Q series programmable controller
Table of Contents

Advertisement

(a) When stored in the standard RAM or SRAM card
Select [Online]
PLC screen.
• Select "Standard RAM" or "Memory card (RAM)" in the "Target memory".
• When the "Target memory" is selected, the name of a file register file is displayed.
• Select the file register file.
• When the
CPU module for the specified number of points.
The file register size can be set in increments of one point. Note that the file always uses 256 points. Even if the range is not
specified from ZR0, the created file will have an assignment from ZR0 to the last number.
For example, when the write range of a file register file is specified to be ZR1000 to ZR1791, the created file will have an
assignment from ZR0 to ZR1791. In this case, the data in ZR0 to ZR999 will be undefined. Specify the file register range
from ZR0. The file register size is checked in increments of 1K points. Specify the file register size in increments of 1K points
starting from R0.
9 - 71
[Write to PLC] from the menu of GX Developer and register a file register file on the Write to
Figure 9.78 Write to PLC screen
button is clicked, the file register file is registered to the specified memory in the
Execute

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents