The following show the examples of the coil and the contact being simultaneously turned on if the values are
set to become "Timer setting value < Scan time + Timer Limit Setting":
When the timer setting value is 1 (1 × 100ms), the scan time is 20ms, and the timer limit setting is
Example
100ms
If the coil of the timer (T0) is turned on at the next scan after the values satisfy "Count at execution of the END
instruction  Timer setting value", the coil and the contact are simultaneously turned on because the values
satisfy "Timer current value = Timer setting value" at the start of the timer.
Timer setting value
(1 100ms)
END
Program
100ms
counting
Count at
execution
0
of the END
instruction
Current
0
value of T0
OFF
X0
OFF
Coil of T0
OFF
Contact
of T0
20ms
Figure 9.29 The coil and the contact are simultaneously turned on with the timer setting value being 1
When the timer setting value is 2 (2 × 100ms), the scan time is 110ms, and the timer limit setting is
Example
100ms
If the coil of the timer (T0) is turned on at the next scan after the values satisfy "Count at execution of the END
instruction  Timer setting value", the coil and the contact are simultaneously turned on because the values
satisfy "Timer current value = Timer setting value" at the start of the timer.
Timer setting value
(2 100ms)
END
Program
100ms
1
counting
Count at
execution
1
of the END
instruction
Current
0
value of T0
OFF
X0
OFF
Coil of T0
Contact
OFF
of T0
110ms
Figure 9.30 The coil and the contact are simultaneously turned on with the timer setting value being 2
Scan time
Timer Limit Setting
(20ms)
END
END
1
0
1
0
20ms
Scan time
Timer Limit Setting
(110ms)
END
END
1
2
1
2
0
0
ON
110ms
Timer setting value
(100ms)
X0
END
0
0
1
ON
ON
ON
20ms
Timer setting value
(100ms)
X0
END
1
1
2
ON
ON
110ms
CHAPTER9 DEVICES
K1
T0
If the coil is turned on for
this period, the contact
is simultaneously turned
on because the count at
execution of the END
instruction becomes
equal to or larger than
the timer setting value.
K2
T0
If the coil is turned on for
this period, the contact
is simultaneously turned
on because the count at
execution of the END
instruction becomes
equal to or larger than
the timer setting value.
9 - 32