(d) Auto refresh with an intelligent function module
This is the time required for refreshing data between the buffer memory of an intelligent function module and
devices in the CPU module.
Use intelligent function module utility package (GX Configurator) for auto refresh settings.
Calculation method
Use the following expression to calculate the auto refresh time with an intelligent function module.
(Refresh time) = KN1 + KN2
For KN1 and KN2, use the values given in Table10.8 and Table10.9.
Table10.8 When an intelligent function module is mounted on the main base unit
CPU module
Q00JCPU
Q00CPU
Q01CPU
Q02CPU
Q02HCPU, Q06HCPU, Q12HCPU, Q25HCPU
Q02PHCPU, Q06PHCPU, Q12PHCPU, Q25PHCPU
Q12PRHCPU, Q25PRHCPU
Table10.9 When an intelligent function module is mounted on the extension base unit
CPU module
Q00JCPU
Q00CPU
Q01CPU
Q02CPU
Q02HCPU, Q06HCPU, Q12HCPU, Q25HCPU
Q02PHCPU, Q06PHCPU, Q12PHCPU, Q25PHCPU
Q12PRHCPU, Q25PRHCPU
When the number of auto refresh points for the analog-digital converter module (Q64AD) is 4
Example
points (when the module is mounted on the Q01CPU main base unit)
(number of refresh points)
0.249(ms) = 0.085 + 0.041
CHAPTER10 CPU MODULE PROCESSING TIME
KN1
115 s
91 s
85 s
53 s
27 s
KN1
120 s
92 s
86 s
61 s
29 s
4
1
10
3
4
5
KN2
55 s
46 s
6
41 s
13 s
7
6 s
8
KN2
56 s
48 s
43 s
15 s
8 s
10 - 11