When the grid voltage varies from the ranges listed in Table 3-1, the KP100G disconnects from the grid.
Table 3-1 Conditions UV/OV of the KP100G
Model
KP100G-OD-ES
KP100G-OD-IT
KP100G-OD-DE
Note: According to VDE0126-1-1 4.2.2, when grid voltage exceeds 115%UN, the KP100G must disconnect from grid within 0.2sec.
According to VDE0126-1-1 4.2.3, the KP100G monitor grid voltage in 10min interval, and when grid voltage exceeds
100%UN in 10min, the KP100G disconnect from grid.
Grid Frequency
When the grid frequency varies from the ranges listed in Table 3-2, the KP100G disconnects from the grid.
KP100G-OD-ES
KP100G-OD-IT
KP100G-OD-DE
ENS standards require that each model be tested by a third-party verification institute, and that all ENS units be tested prior to shipping. To ensure
that switching devices (relays) operate properly, always do an operational check before starting up the KP100G. If the test results are negative, the
KP100G will repeat the self-diagnostics. If the problem remains, it will be necessary to have a specialist diagnose it. Malfunctions are indicated by the