Earthing Requirements - Avaya G860 Installing And Operating

Media gateway
Hide thumbs Also See for G860:
Table of Contents

Advertisement

Table 3: Avaya G860 Media Gateway Version Chassis Dimensions
Dimension
Width
Height
Depth
With projections
Without projections
Weight (Fully loaded)
2.3.1

Earthing Requirements

Connect the equipment enclosure via the provided stud to Protective earth
using No. 6 AWG copper grounding conductor from an approved earthing
electrode.
Metallic parts of network equipment installed in the outside plant shall be
grounded in accordance with Rule 99 of the most recent edition of the
National Electrical Safety Code (NESC), ANSI/IEEE C2.[36]
Safety Earth
Intrinsically, the Avaya G860 Media Gateway chassis must be safety-earthed using an
equipment-earthing conductor. Do not depend on locknut-bushings and double-
locknuts for bonding purposes. Use the earthing hardware provided with the chassis.
Earthing Electrode
The gateway must be earthed to a stable local earth earth reference. The gateway's
earth terminal should be connected thought a separate earth wire (6 recommended) to
the rack's earthing. The earth connection's resistance must not be greater than 0.1
ohm. Verify that the rack's earthing is properly performed.
Value
48.3 cm (19 inches)
22.2 cm (8.75 inches)
36.5 cm (13.7 inch)
30 cm (11.8 inch)
20.45 kg (45.1 lb)
Earthing and Bonding
2. Hardware Overview
Issue 1 October 2007 17

Advertisement

Table of Contents
loading

Table of Contents