Diagnostics
4
A redundant power supply is disconnected from facility power, not properly
installed, or has failed. Verify the power supply is connected to facility power.
1. Ensure the AC power cord associated with the power supply (PS0 or PS1) is
2. Ensure the associated facility circuit breaker is on. If not, ask the customer set
3. Ensure the AC power cord is not damaged. If damaged, replace the cord.
Was a corrective action performed?
YES
5
Verify redundant power supply operation.
1. Inspect the power supply and ensure the amber LED is extinguished.
2. At the HAFM appliance Hardware View, observe the graphic representing
Is a failure indicated?
YES
6
Ensure the indicated power supply is correctly installed and seated in the switch.
If required, partially remove and reseat the power supply.
Was a corrective action performed?
YES
7
Verify redundant power supply operation.
1. Inspect the power supply and ensure the amber LED is extinguished
54
connected to the rear of the switch and a facility power receptacle. If not,
connect the cord as directed by the customer.
the circuit breaker on.
NO
Go to
step
6.
the power supply and ensure a failure symbol (blinking red and yellow
diamond) does not appear.
NO
The switch appears operational. Exit MAP.
NO
Go to
step
8.
Edge Switch 2/24 Service Manual