Input Terminal Functions; Temporarily Switching Operation Between Digital Operator And Control Circuit Terminals - Omron VARISPEED E7 User Manual

Variable torque frequency inverter
Hide thumbs Also See for VARISPEED E7:
Table of Contents

Advertisement

Input Terminal Functions

Temporarily Switching Operation between Digital Operator
and Control Circuit Terminals
The Inverter's run command and frequency reference inputs can be switched between local (i.e., Digital Oper-
ator) and remote (input method set in b1-01 and b1-02).
If any parameter from H1-01 to H1-05 (terminal S3 to S7 function selection) has been set to 1 (local/remote
selection), this input can be used to switch over between local and remote operation.
To set the frequency reference source and RUN command source to control circuit terminals, set b1-01 and
b1-02 to 1.
Related Parameters
Parameter
Number
b1-01
b1-02
Multi-function Digital Inputs (H1-01 to H1-05)
Set Value
NOTE
6-52
Name
Reference selection
RUN command source selection
1
Local/Remote selection (ON: Operator; OFF: Parameter b1-01/b1-02 setting)
Local/remote switching can also be performed using the LOCAL/REMOTE key on the Digital Opera-
tor. When the local/remote selection has been set for one external terminal, the LOCAL/REMOTE key
function on the Digital Operator will be disabled.
Setting
Factory
Range
Setting
Operation
0 to 3
1
0 to 3
1
Function
Change
Access
during
Level
No
Q
No
Q

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents