Input Terminal Functions

Temporarily Switching Operation between Digital Operator and
Control Circuit Terminals
The Inverter run command inputs and frequency reference inputs can be switched between Local and Remote.
Local: The digital operator is used as frequency reference and run command source.
Remote: The frequency reference and run command source can be set in the parameters b1-01 and b1-02.
If any parameter from H1-01 to H1-05 (Digital input terminal S3 to S7 function selection has been set to 1
(local/remote selection), this input can be used to switch over between local and remote.
Related Parameters
Parameter
No.
b1-01
b1-02
Multi-function Digital Inputs (H1-01 to H1-05)
Set Value
1
6
INFO

Inverter Output Baseblock

Using a baseblock command the inverter output can be stopped immediately. In this case the motor will coast
to stop. If the baseblock command is cleared, the inverter output operation is resumed.
If speed search is enabled, the inverter detects the motor speed and the operation is resumed from the detected
speed.
If speed search is disabled, the operation is resumed from the frequency reference which was active before the
baseblock command.
To use the baseblock function one of the digital inputs must be set for baseblock, i.e. H1-
command NO) or H1-
Multi-function Digital Inputs (H1-01 to H1-05)
Set
Value
8
External baseblock NO (Normally Open contact: Baseblock when ON)
9
External baseblock NC (Normally Closed contact: Baseblock when OFF)
Timing Chart
68
6-
Name
Reference selection
RUN command source selection
Local/Remote selection (ON: Operator, OFF: b1-01/02)
Local/Remote switching can also be performed using the LOCAL/REMOTE key on the Digital Oper-
ator. When the Local/Remote function has been set for one external terminal, the LOCAL/REMOTE
key function on the Digital Operator will be disabled.
=9 (baseblock command NC).
Function
Factory
Setting
1
1
Function
Control Methods
Change
during
Open
V/f with
Opera-
V/f
Loop
PG
tion
Vector
No
Q
Q
Q
No
Q
Q
Q
Control Methods
V/f
Open
V/f
with
Loop
PG
Vector
Yes
Yes
Yes
=8 (baseblock
Control Methods
V/f
Open
V/f
with
Loop
PG
Vector
Yes
Yes
Yes
Yes
Yes
Yes
Closed
Loop
Vector
Q
Q
Closed
Loop
Vector
Yes
Closed
Loop
Vector
Yes
Yes