Input Terminal Functions

This section explains input terminal functions, which set operating methods by switching functions for the
multi-function contact input terminals (S3 to S12).
Temporarily Switching Operation between Digital Operator and Control
Circuit Terminals
You can switch the Inverter run command inputs and frequency reference inputs between local (i.e., Digital
Operator) and remote (input method using b1-01 and b1-02).
You can switch between local and remote by turning ON and OFF the terminals if an output from H1-01 to
H1-10 (multi-function contact input terminal S3 to S12 function selection) has been set to 1 (local/remote
selection).
To set the control circuit terminals to remote, set b1-01 and b1-02 to 1 (Control circuit terminals).
Related Constants
Con-
stant
Number
b1-01
b1-02
INFO
-66
6
Name
Description
Display
Reference
Set the frequency reference input
selection
method.
0: Digital Operator
1: Control circuit terminal (analog
input)
Reference
2: MEMOBUS communications
Source
3: Option Card
4: Pulse train input
Operation
Set the run command input
method selec-
method.
tion
0: Digital Operator
1: Control circuit terminal
(sequence input)
Run Source
2: MEMOBUS communications
3: Option Card
You can also perform local/remote switching using the LOCAL/REMOTE Key on the Digital Operator. When
the local/remote function has been set in the external terminals, the LOCAL/REMOTE Key function on the
Digital Operator will be disabled.
Change
during
Setting
Factory
Range
Setting
Opera-
V/f
tion
0 to 4
1
No
Q
0 to 3
1
No
Q
Control Methods
Open
Open
V/f
Flux
Loop
Loop
with
Vec-
Vector
Vector
PG
tor
1
2
Q
Q
Q
Q
Q
Q
Q
Q

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents