Preventing The Motor From Stalling During Acceleration (Stall Prevention During Acceleration Function) - Omron VARISPEED E7 User Manual

Variable torque frequency inverter
Hide thumbs Also See for VARISPEED E7:
Table of Contents

Advertisement

Setting Example
The S-curve characteristic when switching operation (forward/reverse) is shown in the following diagram.
Forward
Reverse
Output frequency
Fig 6.19 S-curve Characteristic during Operation Switching
Preventing the Motor from Stalling During Acceleration
(Stall Prevention During Acceleration Function)
The Stall Prevention During Acceleration function prevents the motor from stalling if a heavy load is applied
to the motor, or sudden rapid acceleration is performed.
If L3-01 is set to 1 (enabled) and the Inverter output current reaches 85 % of the set value in L3-02, the accel-
eration rate will begin to slow down. When L3-02 is exceeded, the acceleration will stop.
If L3-01 is set to 2 (optimum adjustment), the motor accelerates so that the current is held at a level of 50 % of
the inverter rated current. With this setting, the acceleration time setting is ignored.
Related Parameters
Parameter
Number
L3-01
Stall prevention selection during acceleration
L3-02
Stall prevention level during acceleration
Name
Acceleration and Deceleration Characteristics
Change
Setting
Factory
during
Range
Setting
Operation
0 to 2
1
No
0 to 200
120%
No
Access
Level
A
A
6-17