Jump Frequency Function (Operation Avoiding Resonance) - Omron VARISPEED E7 User Manual

Variable torque frequency inverter
Hide thumbs Also See for VARISPEED E7:
Table of Contents

Advertisement

Jump Frequency Function (Operation Avoiding Resonance)

This function allows the prohibition or "jumping" of certain frequencies within the Inverter's output fre-
quency range so that the motor can operate without resonant oscillations caused by some machine systems.
It can also be used for deadband control.
Related Parameters
Parameter
Number
d3-01
Jump frequency 1
d3-02
Jump frequency 2
d3-03
Jump frequency 3
d3-04
Jump frequency width
The relationship between the output frequency and the jump frequency reference is as follows:
Output frequency
Setting Precautions
Set the jump frequencies according to the following formula: d3-01 ≥ d3-02 ≥ d3-03.
When parameters d3-01 to d3-03 are set to 0 Hz, the jump frequency function is disabled.
Name
Frequency reference descending
Jump frequency
width d3-04
Jump frequency
width d3-04
Jump
Jump
frequency 3
frequency 2
(d3-03)
(d3-02)
Fig 6.26 Jump Frequency
Adjusting Frequency References
Setting
Factory
Range
Setting
Operation
0.0 Hz
0.0 to
0.0 Hz
200.0
0.0 Hz
0.0 to
1.0 Hz
20.0
Jump frequency
width d3-04
Frequency reference ascending
Jump frequency reference
Jump
frequency 1
(d3-01)
Change
Access
during
Level
No
A
No
A
No
A
No
A
6-23

Hide quick links:

Advertisement

Table of Contents

Troubleshooting