Setting The V/F Pattern - Omron VARISPEED E7 User Manual

Variable torque frequency inverter
Hide thumbs Also See for VARISPEED E7:
Table of Contents

Advertisement

Setting the V/f Pattern

Using the E1-
ommended to change the settings when the motor is used in open loop vector control mode.
Related Parameters
Parameter
Number
E1-01
E1-03
E1-04
E1-05
E1-06
E1-07
E1-08
E1-09
E1-10
E1-11
E1-12
E1-13
*1. Values for 200 V class Inverters are shown. For a 400 V class Inverter the values have to be doubled.
*2. Parameters E1-11 and E1-12 are disabled when set to 0.0
Setting Inverter Input Voltage
Set the Inverter input voltage correctly in E1-01 so that it matches the power supply voltage. The set value
becomes a reference value for the stall prevention during deceleration and the overvoltage level according to
the table below.
Setting V/f Pattern
The V/f pattern can be selected using parameter E1-03. There are two methods of setting the V/f pattern:
Select one of the 15 preset pattern types (set value: 0 to E), or set a user-defined V/f pattern (set value: F).
The factory setting for E1-03 is F.
To select one of the existing patterns, refer to the following table.
6-100
parameters the Inverter input voltage and the V/f pattern can be set as needed. It is not rec-
Name
Input voltage setting
V/f pattern selection
Max. output frequency (FMAX)
Max. output voltage (VMAX)
Base frequency (FA)
Mid. output frequency (FB)
Mid. output frequency voltage (VB)
Min. output frequency (FMIN)
Min. output frequency voltage (VMIN)
Mid. output frequency 2
Mid. output frequency voltage 2
Base voltage (VBASE)
Inverter
Input Voltage
Voltage Class
Setting E1-01
200 V
200 V
O 400 V
400 V
P 400 V
Change
Setting
Factory
during
Range
Setting
Operation
155 to
*1
No
200 V
*1
255
0 to F, FF
F
No
0.0 to
50.0 Hz
No
200.0
0.0 to
*1
No
200.0 V
*1
255.0
0.0 to
50.0 Hz
No
200.0
0.0 to
2.5 Hz
No
200.0
0.0 to
*1
No
15.0 V
*1
255
0.0 to
1.2 Hz
No
200.0
0.0 to
*1
No
9.0 V
*1
255.0
0.0 to
*2
No
0.0 Hz
200.0
0.0 to
*2
No
0.0 V
*1
255.0
0.0 to
0.0 V
No
*1
255.0
Stall Prevention
OV Level
during Decel Level
410 VDC
377 VDC
720 VDC
662 VDC
820 VDC
754 VDC
Access
Level
Q
A
A
A
A
A
A
A
A
A
A
A

Hide quick links: