Wiring Control Circuit Terminals

Wire Sizes

For remote operation using analog signals, keep the control line length between the Analog Operator or oper-
ation signals and the Inverter to 50 m or less, and separate the lines from main power lines or other control cir-
cuits to reduce induction from peripheral devices.
When setting frequencies from an external frequency source (and not from a Digital Operator), use shielded
twisted-pair wires and ground the shield for the largest area of contact between shield and ground.
Terminal numbers and wire sizes are shown in
Table 2.12 Terminal Numbers and Wire Sizes (Same for all models)
Terminals
Screws
FM, AC, AM, SC, SP,
SN, A1, A2, +V, -V,
S1, S2, S3, S4,
Phoenix
S5, S6, S7
MA, MB, MC, M1,
M2, M3, M4,
R+, R-, S+, S-, IG
E (G)
*1. We recommend using cable-end sleeves on signal lines to simplify wiring and to improve reliability.
Table 2.5
*2. Refer to
for tightening torques for the cable glands.
*3. Use shielded twisted-pair cables to input an external frequency reference.
Table
Possible
Wire
Termi-
Tighten-
Sizes
nal
ing Torque
(N•m)
mm
(AWG)
Single wire
0.14 to 2.5
Stranded
0.5 to 0.6
type
wire:
0.14 to 1.5
(26 to 14)
0.5 to 2
M3.5
0.8 to 1.0
(20 to 14)

Wiring Control Circuit Terminals

2.12.
IP54 Inverters Only
Recom-
Possible
mended
Cable
Clamping
Wire Size
Gland
2
2
mm
Size
(AWG)
*1
:
0.75
*2
M25
(18)
1.25
-
(12)
Wire Type
Cable
Diam.
(mm)
• Shielded, twisted-
9 to 17
*3
pair wire
• Shielded, polyeth-
ylene-covered,
vinyl sheath cable
-
2-27