Omron VARISPEED E7 User Manual page 132

Variable torque frequency inverter
Hide thumbs Also See for VARISPEED E7:
Table of Contents

Advertisement

Setting
Value
Inverter operation ready
6
READY: After start-up or no faults
7
During DC bus undervoltage (UV) detection
8
During baseblock (NO contact, ON: during baseblock)
9
Frequency reference source selection (ON: Frequency reference from Operator)
A
Run command source selection status (ON: Run command from Operator)
B
Load detection NO (NO contact, ON: overload/loss of load detected)
C
Loss of frequency reference (Effective when 1 is set for L4-05)
Fault (ON: Digital Operator communications error or fault other than CPF00 and CPF01 has
E
occurred.)
F
Not used. (Set when the terminal is not used.)
10
Minor Fault (Alarm) (ON: Alarm displayed)
11
Fault reset command active
12
Timer function output
17
Load Detection NC (NC contact, OFF: overload/loss of load detected)
1A
Reverse direction
1E
Restart enabled (ON: Restart enabled)
During motor overload (OL1, including OH3) pre-alarm
1F
(ON: 90% or more of the detection level)
20
OH pre-alarm (temperature reached L8-02)
38
Drive enabled
39
Drive waiting (start delay time b1-11 is active)
3A
During OH and reduced Frequency
3B
RUN command from option card/communications
3D
Cooling fan fault (ON: internal cooling fan error)
Analog Inputs: H3
Parame-
ter Num-
Name
ber
Sets the frequency reference
value when 10 V is input as a per-
H3-02
Terminal A1 gain
centage of the maximum output
frequency set in E1-04.
Sets the frequency reference
value when 0 V is input as a per-
H3-03
Terminal A1 bias
centage of the maximum output
frequency set in E1-04.
Selects the signal level input at
Analog input A2
multi-function analog input A2.
H3-08
signal level selec-
tion
Selects the multi-function analog
input function for terminal A2.
Analog input A2
H3-09
function selec-
Refer to the table
tion.
tings
setting range.
Function
Description
0: 0 to +10V (11 bit).
2: 4 to 20 mA (9-bit input).
3: 0 to 20 mA (9-bit input)
H3-09 Set-
for the explanation of the
Change
Setting
Factory
during
Access
Range
Setting
Opera-
Level
tion
0.0 to
100.0%
Yes
A
1000.0
-100.0
to
0.0%
Yes
A
+100.0
A
0, 2, 3
2
No
*1
2
0 to 1F
No
A
*2
User Parameter Tables
Page
6-65
6-65
6-65
6-65
6-65
6-30
6-44
6-65
-
6-65
6-66
6-86
6-30
6-66
6-45
6-33
6-66
6-66
6-66
6-66
6-66
6-66
MEMO-
BUS
Page
Register
411H
6-21
412H
6-21
417H
6-21
*1
418H
6-21
5-25

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading