Special Considerations for IP54 Inverters of 22 and 30kW capacity
Install the shielded output cable as shown in the
Remove the braided shield on the output cable entirely from the entry hole to the terminal end to avoid short
circuit to the input terminals or the filter.
Installing the Motor Cable at IP54 Inverters of 37 to 55kW capacity
Install the shielded output cable as shown in the figure below. Remove the outer sheath and clamp the braided
shield by the earth clamp.
2-26
Output Cable
Input Cable
(Shielded Cable)
Fig 2.12 Motor Cable Installation for IP54 Inverters of 22 and 30kW
Earth Plate
Earth Clamp
Fig 2.13 Motor Cable Installation for IP54 Inverters of 37 to 55kW
Fig
2.12.
Remove the braided shield entirely
from the entry hole to the terminal end.
Remove the outer sheath
and clamp the braided
shield by the earth clamp
Output Cable
.