Adjusting Frequency References
Adjusting Analog Frequency References
The analog reference values can be adjusted using the gain and bias functions for the analog inputs.
Related Parameters
Parameter
Number
H3-02
Frequency reference terminal A1 input gain
H3-03
Frequency reference terminal A1 input bias
H3-08
Multi-function analog A2 signal level selection
H3-09
Multi-function analog A2 function selection
H3-10
Multi-function analog A2 input gain
H3-11
Multi-function analog A2 input bias
H3-12
Analog input filter time constant
H3-13
Terminal A1/A2 switching
*1. The setting is automatically switched to "B" when the PI controller is enabled
*2. Parameter is moved to Quick Programming Mode when PI controller is enabled.
Adjusting Analog Frequency Reference Using Parameters
The frequency reference can be input from the control circuit terminals using analog voltage or current signals
(analog input A2 only).
The input signal levels can be selected using
•
H3-01 for the analog input A1
H3-08 for the analog input A2
•
Adjustments to the signals can be made using:
•
H3-02 (Gain) and H3-03 (Bias) if analog input A1 is selected to be the frequency reference input
H3-10 (Gain) and H3-11 (Bias) if analog input A2 is selected to be the frequency reference input
•
Refer to
Fig 6.23
for adjusting the signal using the gain and bias functions.
Frequency reference
Terminal A1 input
Name
Frequency reference
Terminal
A1
input voltage
Fig 6.23 Terminals A1 and A2 Inputs
Adjusting Frequency References
Change
Setting
Factory
during
Range
Setting
Operation
0.0 to
100.0%
Yes
1000.0
-100.0
0.0%
Yes
to +100.0
*1
0, 2, 3
No
2
0 to 16
0
No
0.0 to
100.0%
Yes
1000.0
-100.0
0.0%
Yes
to +100.0
0.00 to
0.30 sec.
No
2.00
0 or 1
0
No
0V (4 mA/0 mA)
Terminal A2 input
Access
Level
A
A
*2
A
*2
A
A
A
A
*2
A
Terminal A2 input
voltage (current)
6-21