Improved Operating Performance

This section explains functions for improving motor operating efficiency.
Torque Compensation for Sufficient Torque at Start
and Low-speed Operation
The torque compensation function detects a rising motor load, and increases the output torque.
The inverter calculates the motor primary loss voltage and adjusts the output voltage (V) to compensate insuf-
ficient torque at startup and during low-speed operation. The compensation voltage is calculated as follows:
Motor primary voltage loss × parameter C4-01.
Related Parameters
Parameter
Number
C4-01
Torque compensation gain
C4-02
Torque compensation delay time constant
Adjusting Torque Compensation Gain (C4-01)
Normally, there is no need to change this setting.
Adjust the torque compensation gain under the following circumstances.
If the cable is very long, increase the set value.
If the motor capacity is smaller than the Inverter capacity (max. applicable motor capacity), increase the
set value.
If the motor is vibrating, reduce the set value.
Adjust this parameter so that the output current during low-speed rotation does not exceed the Inverter rated
output current range.
Adjusting the Torque Compensation Primary Delay Time Constant (C4-02)
Set the torque compensation function primary delay in milliseconds.
Normally, there is no need to change this setting. Adjust the parameter under the following circumstances:
If the motor is vibrating, increase the set value.
If the motor response is low, decrease the set value.
Name

Improved Operating Performance

Change
Setting
Factory
during
Range
Setting
Operation
0.00 to
1.00
Yes
2.50
0 to
200 msec
No
10000
Access
Level
A
A
6-27