Omron VARISPEED E7 User Manual page 120

Variable torque frequency inverter
Hide thumbs Also See for VARISPEED E7:
Table of Contents

Advertisement

Param-
eter
Name
Number
Sets the frequency level at which
the snooze operation starts as per-
b5-22 Snooze Level
centage of the max. output fre-
quency.
Snooze Delay
Sets a delay timer for the snooze
b5-23
Time
function
Sets the feedback level at which
b5-24 Wake-Up Level
the inverter wakes up from snooze
operation.
Sets the PI setpoint boost when the
snooze mode is activated. If it is
b5-25 Setpoint Boost
reached once the output will be
switched off. The value is set as
percentage of the PI setpoint.
Maximum Boost
Sets the maximum time the boost
b5-26
Time
operation is performed.
PI Snooze function will only be
activated when the feedback value
b5-27 Snooze feedback
is above this parameter setting.
The value is set as percentage of
the PI setpoint.
Enables or disables the square root
PI Feedback
operation for the PI feedback
b5-28
Square Root
value.
Operation
0: Disabled
1: Enabled
PI Feedback
Sets the gain for the feedback when
b5-29
Square Root Gain
square root operation is enabled.
Selects whether the PI output mon-
itor is shown as square root value
PI Output Moni-
b5-30
or not.
tor Square Root
0: Disable
1: Enable
Selects the units for the PI control-
ler values (b5-19, U1-24, U1-38).
PI unit selec-
b5-31
Refer to table
*2
tion
the explanation of the setting
range.
*1. Parameter is moved into Quick Programming Mode when PI controller is enabled, otherwise the parameter is available only in Advanced Program-
ming Mode.
*2. Parameter function is only valid if a Digital Operator with LCD clear text display is used (LCD or HOA Digital Operator)
b5-31 Settings
Setting
Value
0
WC: Inch of water column
1
PSI: lb/square inch
2
GPM: Gallons per minute
3
F: Degree Fahrenheit
4
CFM: Cubic feet per minute
5
CMH: Cubic meter per hour
6
LPH: Liters per hour
7
LPS: Liters per second
Setting
Description
Range
0 to
100
0 to
3600
0 to
100
0 to
100
0 to
3600
0 to
100
0 or 1
0 to
2.00
0 or 1
b5-31 Settings
for
0 to 11
Function
User Parameter Tables
Change
MEMO-
Factory
during
Access
BUS
Setting
Opera-
Level
Register
tion
0%
Yes
A
1E4H
0 sec.
No
A
1E5H
0%
No
A
1E6H
0%
No
A
1E7H
0 sec.
No
A
1E8H
60%
No
A
1E9H
0
No
A
1EAH
1.00
No
A
1EBH
0
No
A
1ECH
*1
0
No
1EDH
A
Displayed Unit
WC
PSI
GPM
F
CFM
CMH
LPH
LPS
Page
6-87
6-87
6-87
6-87
6-87
6-87
6-87
6-87
6-87
6-87
5-13