Application Parameters: b

Operation Mode Selections: b1
Param-
eter
Number
Reference source
b1-01
selection
RUN command
b1-02
source selection
Stopping method
b1-03
selection
Prohibition of
b1-04
reverse operation
Operation selec-
tion after switch-
b1-07
ing to remote
mode
Run command
b1-08
selection in pro-
gramming modes
5-8
Name
Description
Sets the frequency reference input
method.
0: Digital Operator
1: Control circuit terminal (ana-
log inputs)
2: Serial communications (RS
422/485)
3: Option Card (connected on
CN2)
Sets the run command input
method.
0: Digital Operator
1: Control circuit terminal (digital
multifunction inputs)
2: Serial communications (RS
422/485)
3: Option Card (connceted on
CN2)
Selects the stopping method when
the Run signal is removed
0: Deceleration to stop
1: Coast to stop
2: DC injection to stop
3: Coast to stop with timer (New
Run commands are disregarded
while coasting.)
0: Reverse enabled
1: Reverse disabled
2: Output Phase Rotation (both
rotational directions are
enabled)
3: Output Phase Rotation with
Reverse disabled.
Selects if the Inverter accepts a
Run command that is already set
when the Inverter is switched to
Remote Mode.
0: Preset Run signals are disre-
garded.
(Run signal has to be cycled
once to become active)
1: Preset Run signals become
effective immediately after
switching to the Remote mode.
Selects if a Run signal will be
accepted when the Inverter is in
any Programming Mode.
0: Run signal is disregarded.
1: Run signal is accepted (Dis-
abled for b1-02 = 0).
Change
Setting
Factory
during
Access
Range
Setting
Opera-
Level
tion
0 to 3
1
No
Q
0 to 3
1
No
Q
0 to 3
0
No
Q
0 to 3
0
No
A
0 or 1
0
No
A
0 or 1
0
No
A
MEMO-
BUS
Page
Register
6-5
180H
6-52
6-9
181H
6-52
182H
6-11
183H
6-37
186H
187H