Auto/Hand Mode Switching By Digital Input - Omron VARISPEED E7 User Manual

Variable torque frequency inverter
Hide thumbs Also See for VARISPEED E7:
Table of Contents

Advertisement

Setting precautions
To use the operation source switching function make the following settings:
Set b1-01 (Frequency reference source) to a value different from 2 (Memobus)
Set b1-02 (RUN command source) to a value different from 2 (Memobus)
Set one of the parameters H1-01 to H1-05 to 6B or 6C
Setting for one of
Terminal
H1-01 to H1-05
Status
OFF
6B
ON
OFF
6C
ON

AUTO/HAND Mode Switching by Digital Input

If the HOA Digital Operator (optional available) is connected the Inverter can be switched to AUTO or
HAND mode with digital inputs.
If b1-13 (HAND/AUTO switching during run selection) is set to 1 this is also possible during run, otherwise
the Inverter has to be stopped to enable the switchover. Depending on the setting of b1-13 the functionality of
b1-12 (HAND frequency reference source selection) changes.
Related Parameters
Parameter
Number
b1-12
HAND frequency reference source selection
b1-13
HAND/AUTO switching during run selection
Multi-function Digital Inputs (H1-01 to H1-05)
Set Value
6D
AUTO mode selection (ON: AUTO mode active)
6E
HAND mode selection (ON: HAND mode active)
Application Precautions
Following table shows the behavior of the Inverter depending on the setting of b1-12 and b1-13.
Setting of
Setting of
b1-12
b1-13
0
(Disabled)
0
(Operator)
1
(Enabled)
0
(Disabled)
1
(Terminals)
1
(Enabled)
Frequency Reference and Run Command Source
Inverter
(Frequency reference and Run command source are set in b1-01 and b1-02)
MEMOBUS communication
(Frequency reference and run command are input via Memobus, RS-422/485 port)
MEMOBUS communication
(Frequency reference and run command are input via Memobus, RS-422/485 port)
Inverter
(Frequency reference and Run command source are set in b1-01 and b1-02)
Name
Function
HAND/AUTO Switching Behaviour
Inverter has to be stopped for HAND/AUTO switchover.
If started in HAND mode d1-01 becomes the active frequency reference.
Inverter can be switched over during run.
When switched to HAND mode the last AUTO frequency reference is used in
HAND mode and copied into d1-01.
Inverter has to be stopped for HAND/AUTO switchover.
If started in HAND mode the AUTO frequency reference is used.
Inverter can be switched over during run.
When switched to HAND mode d1-01 becomes the active frequency reference.
Input Terminal Functions
Change
Setting
Factory
during
Range
Setting
Operation
0 or 1
0
No
0 or 1
0
No
Access
Level
A
A
6-61