Set C1-11 to a value other than 0.0 Hz. If C1-11 is set to 0.0 Hz, the function will be disabled.
Acceleration/
deceleration time
switching frequency
(C1-11)
Entering S-curve Characteristics in the Acceleration and Deceleration Time
By performing acceleration and deceleration using an S-curve pattern, shock at start and stop of the machine
can be reduced
Two S-curve characteristic times can be set: At acceleration start and at acceleration end. For deceleration
start and end the S-curve times are fixed to 0.2 sec.
NOTE
6-16
Output frequency
C1-03
C1-01
When output frequency ≥ C1-11, acceleration and deceleration are performed using
Acceleration/deceleration Time 1 (C1-01, C1-02).
When output frequency < C1-11, acceleration and deceleration are performed using
Acceleration/deceleration Time 2 (C1-03, C1-04).
Fig 6.18 Acceleration/deceleration Time Switching Frequency
When S-curve is set, calculate acceleration/deceleration time as follows:
C2-01
+
Accel.Time
=
----------------------------------- -
2
Decel. Time
=
0.2 sec
+
C1-02
C2-02
+
C1-01/03
C1-02/04
C1-04