Connection Diagrams

The connection diagrams of the Inverters are shown in
When using the Digital Operator, the motor can be operated by wiring only the main circuits.
L1
3-phase power
L2
supply
380 to 480 V
L3
50/60 Hz
PE
Multi-function
digital inputs
[Factory settings]
Fig 2.1 Connection Diagram of IP20 Inverters (Model CIMR-E7Z47P51 Shown Above)
2-2
Short-circuit bar
Main
contactor
Fuse
Line
Filter
Forward Run/Stop
Reverse Run/Stop
External fault
Fault reset
Multi-step speed setting 1
Multi-step speed setting 2
Jog frequency selection
Adjustment
Ω
2k
3
0 to 10V
2k Ω
2
1
4 to 20mA
P
P
Input Option Cards
MEMOBUS
communication
RS-485/422
Fig 2.1
and
Fig 2.2
DC reactor to improve input
power factor (optional)
U
X
1
2
Varispeed E7
R/L1
CIMR-
S/L2
E7Z47P51
T/L3
S1
S2
S3
S4
S5
S6
S7
SN
SC
SP
24V
E(G)
Shield
Shield
terminal
terminal
Analog input power supply
+V
+15 V, 20 mA
Analog input 1: Master
A1
frequency reference
Ω
0 to 10 V (20 k
)
Multi-function analog input 1:
A2
[Default: Frequency Bias
Ω
4 to 20 mA (250
)]
AC
0V
-V
Analog input power supply
-15 V, 20 mA
Terminating
resistance
R+
P
R-
S+
P
S-
IG
Twisted-pair
Shielded wires
P
shielded wires
1
Motor
U/T1
M
V/T2
W/T3
2
MA
Fault contact output
MB
250 VAC, 1 A max.
30 VDC, 1 A max.
MC
M1
Contact output 1
M2
[Default: During run]
Multi-function digital
M3
output
Contact output 2
250 VAC, 1 A max.
M4
[Default: Zero speed]
30 VDC, 1 A max.
E(G)
3
Adjustment,
Ω
20 k
Multi-function analog output 1
-
+
(0 to 10 V, 2 mA)
FM
FM
[Default: Output frequency , 0 to 10 V]
Adjustment,
20 k Ω
Multi-function analog output 2
-
+
AM
(0 to 10 V, 2 mA)
AM
[Default: Output power, 0 to 10 V]
AC