Simple Basic Parameterization (Offline); Simple Basic Parameterization (Online) - Siemens SINAMICS G220 Operating Instructions Manual

Table of Contents

Advertisement

Commissioning (Startdrive)
11.3 Device configuration and basic parameterization
11.3.2

Simple basic parameterization (offline)

Procedure
The following steps are required for simple basic parameterization:
1. Create or open project with Startdrive.
2. Create the device configuration in Startdrive offline
– Insert the SINAMICS drive into the project and specify it
– Create and specify SINAMICS components
– Make detailed settings for drive and components
– Optional: Configure user administration and make protection settings for the drive
3. Make basic settings offline via the guided quick startup
4. Load project data into the target device.
5. Establish an online connection between Startdrive and the target device
6. Perform optimization
Result:
The motor rotates.
More information
Detailed information can be found in the information system of the TIA Portal in Chapter
"Configuring SINAMICS G220 drives".
11.3.3

Simple basic parameterization (online)

Procedure
The basic parameterization can also be carried out in online mode as an alternative to offline
mode. The results in the following process sequence:
The following steps are required:
1. Create or open project with Startdrive.
2. Create the device configuration in Startdrive offline
– Insert the SINAMICS drive into the project and specify it
– Create and specify SINAMICS components
– Make detailed settings for drive and components
– Optional: Configure user administration and make protection settings for the drive
3. Download project data to the target device
284
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB
SINAMICS G220 converter