F-Do Configuration; Self-Test Of The Fail-Safe Digital Output - Siemens SINAMICS G220 Operating Instructions Manual

Table of Contents

Advertisement

Functions
14.12 Safety Integrated
14.12.9.12

F-DO configuration

Overview
The F-DO configuration interconnects up to 6 signals of the Safety Integrated Functions with the
failsafe digital output (F-DO).
Requirement
To output the status of a Safety Integrated Function over the F-DO, the Safety Integrated
Function must be enabled.
Description of function
The F-DO configuration interconnects multiple status signals with the failsafe output (F-DO).
ANDing the following signals produces the status of the F-DO:
• Status of the Safety Integrated Functions
• Safe State
The "Safe State" signal is the ORing of the statuses of multiple Safety Integrated Functions.
Parameters
The following list contains the parameters of the "Safe State and F-DO configuration" function.
Number
p9603.0...1
r9722.0...15
r10038
p10039.0...10
c10042[0...5]
14.12.9.13

Self-test of the fail-safe digital output

Overview
The self-test detects whether the fail-safe digital output can be switched into the safe state.
• F-DO 0+ switches to the Low state
• F-DO 0- switches to the High state
The converter responds with a fault if there is an unexpected feedback signal during the
self-test.
702
Name
SI control
SI status signals
SI Safe State status
SI Safe State signal selection
SI F-DO 0 signals of the AND logic operation
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB