Select basic configuration

4.3.1
Select basic type
First, enter the basic type in the unit. Selecting the basic type via menu APPL ID
(Basic configuration) enables or disables functions. The SEZ220 provides the
following basic types:
• M
Empty configuration.
• Mxx
Applications with MIN-MAX-AVR functions.
• Exx
Applications with ENTHALPY function.
• Dxx
Applications with 2X-INV function.
4.3.2
Select programmed application
The unit contains tested, programmed applications. They are described in data
sheet CE1N5146en.
The easiest way to commission the unit is to activate one of these programmed
applications and to adapt the configuration as needed.
Select the application via COMMIS > APPL ID,
and confirm with OK.
Line APPL ID displays: M01
Selection example
This means:
M
Standard application, basic type M.
01 First number of this basic type.
The INFO menu contains data point APPL ID: It provides information on:
• If the programmed application was changed (ADAP = adapted), or
• If it was not changed (ORIG = original).
Note the following on basic type M:
Note on basic type M
• The empty configuration M allows for freely configuring MIN-MAX-AVR
functions. The outputs are undefined.
• Selecting M triggers a reset:
A free configuration are reset to undefined state!
4.3.3
Settings
COMMIS > APPL ID
Path:
Display
Name
APPL ID
Plant type
INFO
Path:
Display
Name
APPL ID
Plant type
SEZ220 signal converter
Commissioning
Range / comment
Set basic type: M, Mxx, Exx, Dxx.
Comment
Displays basic type / adapted or original.
17 / 46
CE1P5146en
02.06.2008