Setting Of Technological Application In Standard Drive Control; Optimized Motor Startup In Standard Drive Control Operating Mode - Siemens SINAMICS G220 Operating Instructions Manual

Table of Contents

Advertisement

Parameters
The following list contains the parameters of the "U/f control with Standard Drive Control"
function.
Number
r0025
r0066
r0071
p0304[0...n]
p0310[0...n]
p0501[0...n]
14.10.2.2

Setting of technological application in Standard Drive Control

Overview
The selected technological application optimizes the calculation of the open-loop and closed-
loop control parameters in Standard Drive Control operating mode.
Description of function
The following settings are available to select for open-loop speed control with parameter p0501.
Table 14-70
0
1
14.10.2.3

Optimized motor startup in Standard Drive Control operating mode

Overview
The startup behavior of the motor can be improved by increasing the current at low speeds.
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB
Name
Output voltage smoothed
Output frequency
Maximum output voltage
Rated motor voltage
Rated motor frequency
Technological application (Standard Drive Control)
Setting of technological application in Standard Drive Control
Constant load (linear characteristic)
Speed-dependent load (parabolic charac‐
teristic)
14.10 Closed-loop drive control
Setting for all applications without speed-dependent
load characteristic
High load torque even at low speeds
Setting, e.g. for parabolic load characteristics for
pumps, fans
Only small load torques at low speeds
Full load is reached at the rated operating point
If high load surges in the range of low and medium
speeds cannot be ruled out, we recommend setting
p501 = 0.
Functions
Unit
[Vrms]
[Hz]
[Vrms]
[Vrms]
[Hz]
 
467