Ac 380 V; Data Regarding The Power Loss In Partial Load Operation - Siemens SINAMICS G220 Operating Instructions Manual

Table of Contents

Advertisement

17.9.4
3 AC 380 V ... 415 V / 3 AC 440 V ... 500 V, degree of protection IP55
Technical data
Table 17-19
Article number
6SL4113-...☐☐-..
F0
08
10
11
12
13
15
16
17
18
20
21
23
24
26
27
The operating point (90/100) means: relative motor stator frequency 90%, relative torque current 100%
1)
Power loss was measured at a pulse frequency of 4 kHz and with space-vector modulation.
17.9.5

Data regarding the power loss in partial load operation

Description
The energy efficiency and power loss data of SINAMICS frequency converters are compliant with
the ecodesign standard IEC 61800-9-2 and the ecodesign regulation (EU) 2019/1781.
The standard IEC 61800-9-2 defines the ecodesign requirements for drive systems in the
low-voltage range, based on an electrically driven machine in frequency converter operation.
Data regarding the power loss in partial load operation are documented in the converter data
sheet. The data sheet is provided in the Siemens Product Configurator in the Internet.
SPC (https://mall.industry.siemens.com/spice/cloudcm/dashboard)
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB
Absolute power loss in W at operating point (90/100)
Rated power
1.1 kW
1.5 kW
2.2 kW
3 kW
4 kW
5.5 kW
7.5 kW
11 kW
15 kW
18.5 kW
22 kW
30 kW
37 kW
45 kW
55 kW
1)
IEC
@ 400 V, 50 Hz
Unfiltered
Filtered
85.5
85.8
96.8
97.3
123
124
156
158
193
196
249
254
325
334
440
448
573
585
557
560
655
660
887
895
1103
1115
1237
1242
1619
1627
Technical data
17.9 Power loss
NEC
@ 480 V, 60 Hz
Unfiltered
Filtered
82.2
82.4
86.5
86.8
108
109
131
132
156
157
217
220
266
271
371
375
476
483
505
507
603
607
764
770
990
1000
1111
1115
1440
1446
817

Advertisement