Save Drive Data To Backup File - Siemens SINAMICS G220 Operating Instructions Manual

Table of Contents

Advertisement

Commissioning (web server)
10.5 Functions and menus
More information
If you want to restore the converter to factory settings with the memory card, see the
information in section "Full reset of all device settings (Page 777)".
10.5.5.2

Save drive data to backup file

Overview
Run the "Save drive data to backup file" function in the following situations:
• After commissioning
• Before drive data is reset using function "Restore factory settings" in the web server
You can find more information in Chapter "Scope of the backup (Page 255)".
• Before drive data is completely reset
You can find more information in Chapter "Full reset of all device settings (Page 777)".
• Before a firmware upgrade/downgrade
Requirement
There are no active converter faults.
Procedure
To save the drive data to a backup file, proceed as follows:
1. Call the "Backup and restore" menu.
2. Press the "Save drive data to backup file" button.
Optional: Assign a name for the backup file.
Result
The drive data is saved to the backup file. The backup file is saved in the download folder of your
operating unit.
Drive data encryption:
• The drive data is not encrypted in the backup file if you deactivated function "Drive data
encryption" in the Security Wizard.
• The drive data is encrypted in the backup file if function "Drive data encryption" is activated
in the Security Wizard and you have configured a drive password.
Description
The "Backup and restore" function is used to restore the drive data for the converter from an
encrypted or unencrypted backup file.
254
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB
SINAMICS G220 converter