Procedure
1. Connect the PROFINET cables to the two PROFINET sockets X150-P1 and X150-P2 on the
controller.
The maximum permitted cable length from the previous station and to the next station is
100 m.
2. Connect the external 24-V power supply to the terminals X124:1,2 and X124:3,4. The
external 24 V supply is only required if communications with the controller is also intended
to run when the line voltage is disconnected.
You have connected the PROFINET cable to the converter.
14.4.2.2

Configuring communication using SIMATIC S7 control

Requirement
Procedure
Proceed as follows to configure communication with a SIMATIC S7 control in PROFINET:
• Install the current Startdrive version.
OR
• Install the GSDML of the converter using "Options/Manage general station description (GSD)"
in the components catalog.
14.4.2.3

Setting communication via PROFINET

Overview
For PROFINET communication between the IO controller and converter, you must set a device
name, an IP address, and a telegram.
Procedure
1. Assign a device name that is unique in the PROFINET network.
PROFINET uses a device name in addition to the MAC address and the IP address to identify
the PROFINET devices.
2. Specify an IP address.
You have the following options to specify the IP address of the converter:
– The IP address is specified using engineering software.
– The IO controller assigns an IP address to the converter.
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB
Functions
14.4 PROFINET communication
327