14.11.16.11 Motor Protection With Temperature Switch; 14.11.16.12 Motor Protection With Temperature Sensor Ptc - Siemens SINAMICS G220 Operating Instructions Manual

Table of Contents

Advertisement

Functions
14.11 Drive functions

14.11.16.11 Motor protection with temperature switch

Overview
To protect the motor against overtemperature, the converter can evaluate a temperature switch,
such as a bimetal switch.
Description of function
The converter interprets a resistance ≥ 100 Ω as an open bimetallic switch and responds
according to the setting for p0610.
Parameters
The following list contains the parameters of the "Motor protection with temperature switch"
function.
Number
p0335[0...n]
p0601[0...n]
p0610[0...n]

14.11.16.12 Motor protection with temperature sensor PTC

Overview
To protect the motor against overtemperature, the converter can evaluate a PTC sensor.
Description of function
The converter interprets the resistance as follows:
• Resistance > 1650 Ω: Overtemperature
The converter responds according to the setting for p0610.
• Resistance < 20 Ω: Short-circuit
The converter responds with alarm A07015.
If the alarm is present for longer than 100 milliseconds, the converter shuts down with fault
F07016.
Parameters
The following list contains the parameters of the "Motor protection with temperature sensor
PTC" function.
Number
p0335[0...n]
p0601[0...n]
630
Name
Motor cooling type
Motor temperature sensor type
Motor overtemperature response
Name
Motor cooling type
Motor temperature sensor type
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB
Unit
 
 
 
Unit
 
 
SINAMICS G220 converter

Advertisement

Table of Contents
loading