Communication test

This function checks if transient transmission data can be properly routed from the own station to the communication target.
Depending on selection for "Communication Method" ("Network No./Station No." or "IP Address"), the range that can be
checked may vary.
Selection of "Communication
Method"
Network No./Station No.
IP Address
The following explains the procedure for a communication test.
Precautions
• When a relay sending station is set to "Target Station", the communication test ends with an error. Set a relay receiving
station to "Target Station".
Network No.1
Station
Station
No.0
No.1
Relay
Own station
receiving
(request source)
station
• When "Network No./Station No." is selected for "Communication Method" and a station mounted on the same system
(module connected with a connector or cable) is set for "Target Station", the communication test ends with an error.
• This test cannot check whether transient transmission can be performed from the connected station (own station) to a
station on another network by specifying an IP address.
• Since this function uses PING, the error "a communication test target station communication error" (error code D919H)
occurs if the communication target does not respond to PING. When executing this function, check if the security setting
(such as firewall) of the communication target is set to respond to PING. Moreover, if the target is set not to respond to
PING in the security settings (such as a firewall), it may take some time until a timeout error occurs on the engineering tool.
For details on when communication of the engineering tool is not allowed in the firewall settings of Windows, refer to the
following.
 GX Works3 Operating Manual
8 TROUBLESHOOTING
136
8.3 Checking the Network Status
Communication target of transient transmission
Stations on the same network
 Available for check
 Available for check
Network No.2
Station
Station
No.2
No.0
Relay
sending
station
Stations on the other network
 Not available for check
 Not available for check
1.
Display the "Communication Test" window and select
"Network No./Station No." or "IP Address" from
"Communication Method".
[Diagnostics]  [CC-Link IE TSN/CC-Link IE Field
Diagnostics]  [Communication Test] button
2.
Enter values for "Target Station" and "Communication
Data Setting".
3.
Click the [Execute Test] button to execute the
communication test. If an error occurs, take corrective
actions according to the error message.