• When all the device stations are CC-Link IE TSN Class A, they can be connected up to the maximum
number of connectable stations specified in the CC-Link IE TSN performance specifications.
• To branch the network with a firmware version of "1.001" or earlier, a general-purpose switching hub can be
used.
• To branch the network with a firmware version of "1.002" or later, a TSN switching hub or general-purpose
switching hub can be used. When using a TSN switching hub, set "TSN HUB Setting" to "Use TSN HUB".
• Set "Connection Device Information" of the master station parameters to "Mixture of CC-Link IE TSN Class
B/A or CC-Link IE TSN Class A Only". In addition, because the Motion module with a firmware version of
"1.001" or earlier does not support 100 Mbps communication, refer to the following.
Page 91 If a switching hub is used to configure a system (master station: 1 Gbps)
■If a switching hub is used to configure a system (master station: 100 Mbps)
The following figure shows connection of the Motion module (100 Mbps) + inverters. (Only the master station is CC-Link IE
TSN Class B.)
No.0
Class B (100 Mbps)
No.0: Motion module (master station)
No.1, No.2, No.3, No.4, No.5: Inverter (remote station)
• When all the device stations are CC-Link IE TSN Class A, they can be connected up to the maximum
number of connectable stations specified in the CC-Link IE TSN performance specifications.
• To branch the network with a firmware version of "1.001" or earlier, a general-purpose switching hub can be
used.
• To branch the network with a firmware version of "1.002" or later, a TSN switching hub or general-purpose
switching hub can be used. When using a TSN switching hub, set "TSN HUB Setting" to "Use TSN HUB".
• Connection after the TSN switching hub or general-purpose switching hub can be a line topology, star
topology, and coexistence of line and star topologies.
• Set "Connection Device Information" of the master station parameters to "Mixture of CC-Link IE TSN Class
B/A or CC-Link IE TSN Class A Only". In addition, because the Motion module with a firmware version of
"1.001" or earlier does not support 100 Mbps communication, refer to the following.
Page 91 If a switching hub is used to configure a system (master station: 1 Gbps)
4 SYSTEM CONFIGURATION
92
4.5 Connection Examples
No.1
Class A (100 Mbps)
General-purpose
switching hub
or
TSN switching hub
No.2
Class A (100 Mbps)
No.4
Class A (100 Mbps)
No.3
Class A (100 Mbps)
No.5
Class A (100 Mbps)