■Coexistence of line and star topologies
Line and star topologies can be mixed in the same network configuration.
• When the master station with a communication speed of 1 Gbps and a remote station with a communication speed of 100
Mbps exist in the structure, set "Communication Period Setting" to "Low-Speed" for the remote station with a
communication speed of 100 Mbps.
No.0 (1 Gbps)
No.0 (1 Gbps)
No.0: Master station
No.1, No.2, and No.3: Remote station
• When the communication speed for the master station is 1 Gbps, connection cannot be made if the total cyclic data size of
all device stations on the 100 Mbps device side, including the devices with a communication speed of 100 Mbps that form a
boundary between the communication speed of 1 Gbps and 100 Mbps, exceeds 2K bytes.
No.0
No.1
(1 Gbps)
(1 Gbps)
No.0: Master station
No.1, No.2, No.3, No.4, No.5, and No.6: Remote station
 Set the total cyclic data size within 2K bytes.
No.1 (1 Gbps)
TSN switching
hub
No.1 (1 Gbps)
TSN switching
hub
No.2
(1 Gbps)
No.3
(1 Gbps)
4.1 Structure of CC-Link IE TSN Class B devices and Ethernet devices
No.2 (100 Mbps)
No.3 (100 Mbps)
Low speed
Low speed
No.2 (100 Mbps)
No.3 (100 Mbps)
Low speed
Basic cycle
Ò
No.4
(100 Mbps)
TSN switching
hub
No.5
(100 Mbps)
No.6
(100 Mbps)
4 SYSTEM CONFIGURATION
4
59

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-f fx5-40ssc-gMelsec iq-f fx5-80ssc-g

Table of Contents