Supplementary cyclic settings
Set the station-based block data assurance and I/O maintenance settings.
Item
Station-based Block Data Assurance
I/O Maintenance
Output Hold/
Settings
Clear Setting
during CPU
STOP
Data Link Error
Station Setting
Output Mode
upon CPU Error
Transient transmission group No. setting
Set the transient transmission group number.
Item
Transient Transmission Group No.
Setting
Parameter name
Set a name for the module parameter if desired.
Item
Parameter Name
Module operation mode
Set the mode for the Motion module.
Item
Module Operation Mode
5 PARAMETER SETTINGS
106
5.4 Application Settings
Description
Select whether to ensure data integrity of the data blocks being refreshed
between the CPU module and the Motion module. (Page 29 Cyclic data
assurance)
Select whether cyclic data output is held or cleared when the CPU module
mounted with the Motion module is set to the STOP state. (Page 32 I/O
maintenance settings)
Select whether input data from the master station is held or cleared when a data
link error occurs. (Page 32 I/O maintenance settings)
Select whether cyclic transmission output data is held or cleared when a stop
error occurs in the CPU module mounted with the Motion module. (Page 32
I/O maintenance settings)
Description
Set the group number to perform transient transmission using group
specification.
Description
Set a name for the module parameter if desired.
Description
Online
Select this mode to connect the Motion module to the network for performing data
link with other stations.
Setting range
• Enable
• Disable
(Default: Enable)
• Hold
• Clear
(Default: Hold)
• Clear
• Hold
(Default: Clear)
• Clear
• Hold
(Default: Clear)
Setting range
0 to 32 (0: No group specification)
(Default: 0)
Setting range
Up to 8 one-byte or two-byte
characters
(Default: empty)
Setting range