Mitsubishi Electric MELSEC iQ-F FX5 Series User Manual page 112

Motion module
Hide thumbs Also See for MELSEC iQ-F FX5 Series:
Table of Contents

Advertisement

Simple
Detailed
display
display
Reserved/Error Invalid Station
Communication Period Setting
CC-Link IE TSN Class Setting
Station Information
*1 When the RX/RY start address, end address, or points are equal to 20h, the RX/RY data is guaranteed to be 32bit data.
*2 If it is set for the device station that supports CANopen communication in the Motion module with the firmware version "1.001" or earlier,
the error "Network parameter error" (error code: 2221H) occurs.
Because a portion of the setting items are not displayed in simple display, when there are deficiencies in
setting items that are not displayed, the "Output" window may display a warning or error by selecting [Close
with Reflecting the Setting].
If a warning is displayed, switch to detailed display and correct the items.
5 PARAMETER SETTINGS
110
5.5 "CC-Link IE TSN Configuration" Window
Description
Set the device station as a reserved station or error invalid station.
• No Setting: The device station is connected to the network.
• Reserved Station: The device station is reserved for future expansion. By
using a reserved station, link device assignment will not change even if the
device station is added (reservation is canceled). Therefore, modification
of the program is not required. Physical connection of the device station on
the network is not required.
• Error Invalid Station: Even if a device station is disconnected during data
link, the master station will not detect the device station as a faulty station.
This setting is not available for Motion control stations.
When multiple communication cycles are set, set the cycle of each device
station. (Page 31 Communication cycle coexistence)
Set master control stations to "Basic Period".
Set the CC-Link IE TSN Class of the device for each device station.
■Alias
Enter the name of a device if required.
The name entered is displayed in "Network Status" of the "CC-Link IE TSN/
CC-Link IE Field Diagnostics" window.
For the extension module of the remote station, the name is not displayed in
the "CC-Link IE TSN/CC-Link IE Field Diagnostics" window, even if entered.
■Comment
Information entered in "Comment1" on the "Properties" window displayed by
right-clicking the module in the list of stations or the network map is
displayed.
■Station-specific mode setting
Set the station-specific mode of the device station. (Only when the device
station supports the station-specific mode)
Setting range
• No Setting
• Reserved Station
• Error Invalid Station
(Default: No setting, master station is fixed as
empty)
• Basic Period
*2
• Normal-Speed
*2
• Low-Speed
(Default: Basic cycle, master station is fixed
as empty)
• CC-Link IE TSN Class B
• CC-Link IE TSN Class A
(Default: Varies depending on the device)
Up to 32 one-byte characters (one-byte or
two-byte)
(Default: empty)
Up to 32 one-byte characters (one-byte or
two-byte)
(Default: empty)
The setting varies depending on the set
device station.