Mitsubishi Electric MELSEC iQ-F FX5 Series User Manual page 197

Motion module
Hide thumbs Also See for MELSEC iQ-F FX5 Series:
Table of Contents

Advertisement

No.
Name
SW00C8 to
Parameter setting status
SW00CF
SW00D0 to
Error invalid station setting status
SW00D7
SW00E8 to
Station type match status
SW00EF
SW00F0 to
CPU operating status of each station
SW00F7
SW0100 to
CPU moderate/major error status of each
SW0107
station
SW0110 to
CPU minor error status of each station
SW0117
SW0160 to
Execution result of device station
SW0167
parameter automatic setting function
SW0194
Detailed execution result of device station
parameter automatic setting
SW01A0 to
CC-Link IE TSN Protocol version 2.0
SW01A7
support status for each station
SW04A0
Time synchronization method
SW04B0 to
Station time synchronization status
SW04B7
Description
Stores the status of parameter settings.
0: No parameter setting
1: Parameter set
(Conditions)
• Stations that surpass the maximum station number are ignored.
Stores the error invalid station setting status of each station.
0: Station other than an error invalid station
1: Error invalid station
(Conditions)
• Stations that surpass the maximum station number are ignored.
Shows the match status of the parameters with the station types. (This is available only for the
number of connected stations.)
0: Station type matched
1: Station type mismatch
Stores the CPU operating status of each station.
0: RUN or PAUSE
1: STOP or moderate/major error
(Conditions)
• Reserved stations and stations that surpass the maximum station number are ignored.
• Since a local station cannot obtain the station information of the CC-Link IE TSN Class A
remote station when communicating in multicast mode, "0: RUN, PAUSE" is reflected to the
CC-Link IE TSN Class A remote station.
Stores the CPU moderate/major error occurrence status of each station in the local station.
Stores the moderate/major error occurrence status of each station in the remote station.
0: No moderate/major error
1: Moderate/major error occurring
(Conditions)
• If an error occurs, data prior to error is held.
• Reserved stations and stations that surpass the maximum station number are ignored.
• Since a local station cannot obtain the station information of the CC-Link IE TSN Class A
remote station when communicating in multicast mode, "0: No moderate/major error" is
reflected to the CC-Link IE TSN Class A remote station.
Stores the CPU minor error occurrence status of each station in the local station.
Stores the minor error occurrence status of each station in the remote station.
0: Normal, or a moderate or serious error occurring
1: Minor error occurring
(Conditions)
• Reserved stations and stations that surpass the maximum station number are ignored.
• Since a local station cannot obtain the station information of the CC-Link IE TSN Class A
remote station when communicating in multicast mode, "0: Normal, or a moderate or serious
error occurring" is reflected to the CC-Link IE TSN Class A remote station.
When the device station parameter automatic setting is completed with an error, the bit of the
target station is turned on.
On: Completed with an error
Off: Completed successfully
When the setting is completed with an error, the error code is stored in 'Detailed execution result
of device station parameter automatic setting' (SW0194).
When completed with an error caused by the master station, the bit is not turned on.
When the device station parameter automatic setting is completed with an error, the error code
is stored.
When completed with an error caused by the device station, the bit of the target station of
'Execution result of device station parameter automatic setting function' (SW0160 to SW0167) is
turned on.
The CC-Link IE TSN Protocol version 2.0 support status for each station is stored.
0: Not supported
1: Supported
(Condition)
• Stations that surpass the maximum station number are ignored.
Stores the time synchronization method.
0: IEEE1588
1: IEEE802.1AS
Stores the time synchronization status for each station.
0: Time asynchronous station
1: Time synchronized station
For time synchronized stations, the time synchronization method can be found in 'Time
synchronization method' (SW04A0).
(Condition)
Stations that surpass the maximum station number are ignored.
Appendix 3 List of Link Special Register (SW)
A
APPX
195

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-f fx5-40ssc-gMelsec iq-f fx5-80ssc-g