Error
Error definition and causes
code
C052H
The number of read/write points from/to
the device of SLMP message is out of the
allowable range in the CPU module (in
units of bits).
C053H
The number of read/write points from/to
the random device of SLMP message is
out of the allowable range in the CPU
module (in units of bits).
C054H
The number of read/write points from/to
the random device of SLMP message is
out of the allowable range in the CPU
module (in units of words, double words).
C055H
The read/write size from/to the file data of
SLMP message is out of the allowable
range.
C056H
The read/write request exceeds the largest
address.
C057H
The request data length of the SLMP
message does not match the number of
data in the character (a part of text).
C058H
The request data length of the SLMP
message after the ASCII/binary conversion
does not match with the number of data in
the character (a part of text).
C059H
• The specified command and
subcommand of the SLMP message are
incorrect
• A function that is not supported by the
target device was executed.
C05AH
The Ethernet-equipped module cannot
read/write data from/to the device specified
by the SLMP message.
C05BH
The Ethernet-equipped module cannot
read/write data from/to the device specified
by the SLMP message.
C05CH
• The received request data of the SLMP
message is incorrect.
• The setting value of the communication
setting when the iQSS function is
executed is out of range.
• When the iQSS function is executed, the
items of communication setting which
cannot be set on the target device are
set.
• When the iQSS function is executed, the
required setting items have not been set
to the target device.
C05DH
The "Monitor Request" command is
received before the monitor registration is
performed by the "Monitor Registration/
Clear" command of the SLMP message.
8 TROUBLESHOOTING
154
8.5 List of Error Codes
Action
Correct the number of read/write points and send the SLMP
message to the Ethernet-equipped module again.
Correct the number of read/write points and send the SLMP
message to the Ethernet-equipped module again.
Correct the number of read/write points and send the SLMP
message to the Ethernet-equipped module again.
Correct the read/write size and send the SLMP message to the
Ethernet-equipped module again.
• Correct the start address or the number of read/write points so
that the request does not exceed the largest address and send
the data to the Ethernet-equipped module again.
• If the access target and connection stations are modules of the
MELSEC iQ-R series, send the SLMP message again to the
Ethernet-equipped module using 003 and 002 of
subcommands.
Check and correct the text or request data length, and send the
SLMP message to the Ethernet-equipped module again.
Check and correct the text or request data length, and send the
SLMP message to the Ethernet-equipped module again.
• Check that there are no errors in the specification of the
command and subcommand of the SLMP message.
• Check whether the function executed is supported by the target
device.
• Check the version of the target device.
Correct the specification of the device to be read/written and send
the SLMP message to the Ethernet-equipped module again.
Correct the specification of the device to be read/written and send
the SLMP message to the Ethernet-equipped module again.
• Correct the request data and send the SLMP message to the
Ethernet-equipped module again.
• Correct the setting details of when the iQSS function is executed,
and retry the operation.
Register the monitoring data using "Monitor Registration/Clear"
command and perform monitoring.
Detailed information 1
Detailed information 2