Connected/Disconnected module detection

Connected device stations are detected and displayed on the "CC-Link IE TSN Configuration" window.
1.
Click the [Connected/Disconnected Module Detection] button.
2.
When the [Execute] button is clicked according to the instruction on the window, connected device stations are detected
and displayed on the "CC-Link IE TSN Configuration" window.
3.
Check items in the list of stations and change them as necessary. (Page 109 Setting items)
4.
Select [Close with Reflecting the Setting] and close the "CC-Link IE TSN Configuration" window.
Detection of connected/disconnected devices cannot be executed in the following cases.
• The Motion module is not in online mode. (Page 106 Module operation mode)
• The actual system configuration is incorrect. (Such as IP address duplication)
• The master station does not perform data link.
Connection/Disconnection/Replacement
When the [Connected/Disconnected Module Detection] button is clicked while the saved CC-Link IE TSN configuration is
displayed, IP addresses of detected device stations are compared with the saved IP addresses of device stations and
displayed as follows by connection/disconnection/replacement.
IP address verification
result
Detected device stations are in
the saved CC-Link IE TSN
structure.
Device stations in the saved CC-
Link IE TSN structure are not
detected.
Operation
Display
Replace
When parameters between a detected device station and a saved CC-
Link IE TSN structure mismatch, the parameters are replaced with the
parameters of the detected device station.
When the model name, model version, and station type are
mismatched, the following settings are inherited.
• "RX Setting", "RY Setting", "RWr Setting", "RWw Setting"
• "IP Address" of the master station
• "Subnet Mask"
• "Default Gateway"
• "Reserved/Error Invalid Station" (however, if "Reserved Station" is set,
the setting will change to the default.)
• "Network Synchronous Communication"
• "Communication Period Setting"
If only the station number is mismatched, only the station number is
reflected, and all the settings are inherited.
(However, if the station number of the detected device has not been set,
the station number of the device before replacement is inherited.)
Disconnect
• Modules other than extension modules: Setting of "Reserved/Error
Invalid Station" is changed to "Reserved Station".
• Extension modules: Are deleted.
When station numbers of
detected device stations
are not set
The station number takes over
the station number of the saved
CC-Link IE TSN structure.
5 PARAMETER SETTINGS
5.5 "CC-Link IE TSN Configuration" Window
5
111