Refresh Settings - Mitsubishi Electric MELSEC iQ-F FX5 Series User Manual

Motion module
Hide thumbs Also See for MELSEC iQ-F FX5 Series:
Table of Contents

Advertisement

Refresh settings

Assign link refresh ranges between the following devices.
• SB, SW, link devices (RX, RY, RWr, RWw) of the Motion module  Devices of the CPU module
Setting method
The procedure for the refresh settings is as follows.
1.
Set the required items.
2.
Click the [Apply] button to finish "Refresh Settings".
Setting items
The setting items for the refresh settings are as follows.
Item
Description
Device Assignment
Right-click in the setting window and select a link device assignment method
Method
from the "Device Assignment Method" menu.
• Start/End: Enter the start and end numbers of link devices.
• Points/Start: Enter the numbers of points and start numbers of link devices.
Link Side
Set the link refresh ranges of SB and SW. One link refresh range can be set for
each of SB and SW. ( Page 27 Link refresh)
Ex.
00000H
·
001FFH
00000H
·
CPU Side
001FFH
Device name
(SB)
Device name
(SW)
Motion module
Setting range
• Start/End
• Points/Start
(Default: Start/End)
■Device Name
• SB (fixed)
• SW (fixed)
■Points
• SB: 16 to 4096 (set in increments of 16 points)
• SW: 1 to 4096
(Default: empty)
■Start
• SB: 0H to FF0H (set in increments of 16 points)
• SW: 0H to FFFH (set in increments of 1 point)
(Default: empty)
00000H
Device name
·
■End
(SB)
• SB: FH to FFFH (set in increments of 16 points)
001FFH
• SW: 0H to FFFH (set in increments of 1 point)
00000H
(Default: empty)
Device name
·
(SW)
■Target
001FFH
• Specify Device
(Default: empty)
■Device name
• Specify Device (link side is SB): SB, M, L, B, D,
R
• Specify Device (link side is SW): SW, M, L, B, D,
R
CPU module
(Default: empty)
■Points, End
Displayed according to setting of "Start".
(Default: empty)
■Start
Device range of CPU modules (Set bit devices in
increments of 16 points and word devices in
increments of 4 points.)
(Default: empty)
5 PARAMETER SETTINGS
5.3 Basic Settings
5