Mitsubishi Electric MELSEC iQ-F FX5 Series User Manual page 151

Motion module
Hide thumbs Also See for MELSEC iQ-F FX5 Series:
Table of Contents

Advertisement

Error
Error definition and causes
code
1C4AH
Connection with a slave device that does
not support Motion control station was
detected.
1C4BH
A Motion control station setting error was
detected.
1D10H
System error
to 1D11H
1D20H
System error
1D21H
System error
20E0H
The module cannot communicate with the
CPU module.
2160H
IP address duplication was detected.
2220H
The parameter setting is corrupted.
2221H
• The set value is out of the range. Or the
setting values of the master station and
local stations are not consistent.
• Parameters that are not supported by
the firmware version of the Motion
module have been set.
24C0H
System error
to
24C3H
24C6H
System error
2600H
System error
2610H
System error
2611H
System error
3000H
System error
3004H
System error
3009H
The result when the value set in
"Communication Period Interval Setting" in
"Communication Period Setting" under
"Basic Settings" of the master station is
multiplied by "Communication Period
Setting" of the device station set in
"Network Configuration Settings" under
"Basic Settings" is out of the range.
300AH
• The combination of the local station
firmware version and the master station
firmware version is incorrect.
• The set value is out of the range. Or the
setting values of the master station and
local stations are not consistent.
Action
Connect a slave device that supports Motion control station.
For connectable slave devices, refer to "Devices Compatible with
CC-Link IE TSN [FX5-SSC-G]" the following manual.
MELSEC iQ-F FX5 Motion Module/Simple Motion Module
User's Manual (Application)
• Check that a Motion control station is set for "(Pr.141) IP
address".
• Check if "(Pr.141) IP address" is set for an axis that exceeds
"(Pr.152) Control axis number upper limit".
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
The hardware failure of the CPU module may have been occurred.
Please consult your local Mitsubishi representative.
Check the IP addresses.
Check the detailed information of the error in "Module Diagnostics"
of the engineering tool, and write the displayed parameter. If the
same error occurs again, the possible cause is a hardware failure
of the module. Please consult your local Mitsubishi representative.
• Check the detailed information of the error in "Module
Diagnostics" of the engineering tool, and correct the parameter
setting corresponding to the parameter number.
• Check the firmware version of the Motion module. If parameters
that are not supported are set, update the firmware version or
correct the parameters.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Check the detailed information in "Module Diagnostics" of the
engineering tool. Correct the parameter settings described below
so that the result when the value set in "Communication Period
Interval Setting" in "Communication Period Setting" under "Basic
Settings" of the master station is multiplied by "Communication
Period Setting" of the device station set in "Network Configuration
Settings" under "Basic Settings" becomes within 16ms.
• "Communication Period Interval Setting" in "Basic Settings"
• "Communication Period Setting" of the relevant device station in
"Network Configuration Settings"
Set a value to "Communication Period Setting" of device stations
by selecting a multiple value on "Multiple Period Setting" of
"Communication Period Setting" under "Basic Settings".
• Check the firmware versions of the master station and local
station. If the combination is incorrect, update the firmware
version of the older local station or that of the master station.
• Check the detailed information of the error in "Module
Diagnostics" of the engineering tool, and correct the parameter
setting of the master station corresponding to the parameter
number. If the same error occurs again, the possible cause is a
hardware failure of the module. Please consult your local
Mitsubishi representative.
Detailed information 1
Detailed information 2
■Parameter information
• Parameter type
■
■Parameter information
• Parameter type
• Intelligent module No.
• Parameter No.
• Network No.
• Station No.
■
■
■Target station information
• Station Number
• IP address
■Parameter information
• Parameter type
• Intelligent module No.
• Parameter No.
• Network No.
• Station No.
■
8 TROUBLESHOOTING
149
8.5 List of Error Codes
8

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-f fx5-40ssc-gMelsec iq-f fx5-80ssc-g

Table of Contents