5 PARAMETER SETTINGS

5.1.2 Network settings

5 - 6
These parameters are used to configure the MELSECNET/H network.
Set the starting I/O No., network No., total number of (slave) stations, group No. and
mode for each of the module model names set in the number of module cards settings.

(1) Starting I/O No.

Set the starting input/output number to which the module is loaded in 16-point
units in hexadecimal for each applicable network module.
For example, set 130 when the network module is loaded onto X/Y130 to 14F.
Q61P
QCPU QX42
64 pts 64 pts 32 pts 32 pts 32 pts 32 pts
00
H
X/Y
to
3F
H
(a) Valid setting range
0
to 0FE0
H
H
(b) Precaution
Unlike the setting method for the AnUCPU (where the higher two digits of
the 3-digit value should be set), here all three digits should be set as is.

(2) Network No.

Set the network number to which the applicable network module is connected.
(a) Valid setting range
1 to 239

(3) Total (slave) stations

Set up the total number of multiplexed remote sub-master stations, remote I/O
stations, and reserved stations in a single network.
CPU QJ71
1M
QJ72
I/ O
1R1
(a) Enabled setting range
1 to 64
QX42
QX41
QY41
QY41
40
80
A0
C0
H
H
H
H
to
to
to
to
7F
9F
BF
DF
H
H
H
H
Remote master station
Total (slave) stations
3
R
Network No.1
QJ72
Reserved
stations
1R2
QY41
QJ71
Vacant
48 pts
32 pts
E0
100
130
H
H
H
to
to
to
FF
12F
14F
H
H
H
QJ72
I/ O
1R3
MELSEC-Q