Upgrade a two-cabinet system with metal cable to Option 11C
553-3021-250
Standard 7.00
Figure 10
NTAK1204 or NTAK1205 cable connection
7
Remove the ground connection from the ground lug in the main
cabinet.
8
Install a ground block in the area of the main cabinet.
Route the ground wire to the ground block. Install a ground wire from
the block to the ground lug in the main cabinet (see Figure 11 on page
49).
Use #6 AWG (40 Metric) ground wire. For more information about
grounding, refer to the Option 11C Planning and Installation Guide
(553-3021-210).
Note 1: Grounding methods vary depending on the type of
cross-connect terminal used. You do not always need an NTBK80
grounding block (such as with the Krone Test Jack Frame used in
some countries). Refer to the Option 11C Planning and Installation
(553-3021-210)
Guide
Note 2: Do not install a ground wire to the existing expansion cabinet.
Install a ground wire to the expansion cabinet when the new expansion
cabinet is in position.
April 2000
NTAK1204 or NTAK1205 Cable
for more information.