Mode 4: Rise Time (Default: 0.0 S); Mode 5: Fall Time (Default: 0.0 S); Mode 10: Hw Write Protection (Default: Off, Display - -) - Siemens Pointek CLS200 Operating Instructions Manual

Hide thumbs Also See for Pointek CLS200:
Table of Contents

Advertisement

7.2.5

Mode 4: Rise time (default: 0.0 s)

Rise Time is a delay setting which adjusts the response time of the signal
becoming covered (Rising Edge). It affects the Primary Value of the Transducer Block. Possible
values range from 0.0 to 100.0 s, in 0.1 s intervals.
This symbol to the left of the numerical value on the display indicates a Rise Time setting.
To set Rise Time:
• Select Mode 4.
• Press ⇑ or ⇓ to open Edit Mode.
• Press ⇑ to adjust the value digit by digit.
• Press ⇓to save the value.
• Press M to exit.
The bar graph, and numerical value in counts, continue to respond instantaneously to
1)
changes in level.
7.2.6

Mode 5: Fall time (default: 0.0 s)

Fall Time is a delay setting which adjusts the response time of the signal
becoming uncovered (Falling Edge). It affects the Primary Value of the Transducer Block.
Possible values range from 0.0 to 100.0 s, in 0.1 s intervals.
This symbol to the left of the numerical value on the display indicates a Fall Time setting.
To set Rise Time:
• Select Mode 5.
• Press ⇑ or ⇓ to open Edit Mode.
• Press ⇑ to adjust the value digit by digit.
• Press ⇓to save the value.
• Press M to exit.
The bar graph, and numerical value in counts, continue to respond instantaneously to
1)
changes in level.
7.2.7
Mode 10: HW Write Protection (default: OFF, display – –)
Note
When HW Write Protection is enabled, L appears in the Mode display field, in normal
measuring mode.
Pointek CLS200/CLS300 digital
Operating Instructions, 05/2021, A5E47904060-AA
7.2 Programming via the Local User Interface (LUI)
Local operation
to the sensor
1)
to the sensor
1)
43

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pointek cls300

Table of Contents