Siemens Pointek CLS200 Operating Instructions Manual page 68

Hide thumbs Also See for Pointek CLS200:
Table of Contents

Advertisement

Remote operation
9.2 Status
Extended diagnostics
Extended diagnostic messages
Meaning
Electronic temperature
exceeds permissible range
Sensor value exceeds
diagnostic alarm limits
Calibration timer,
unacknowledged alarm
Calibration timer,
unacknowledged warning
Service timer, unacknowl-
edged alarm
Service timer, unacknowl-
edged warning
Sensor value exceeds
sensor limits
Sensor Test Running
Memory checksum error
Sensor test failed
Sensor value simulation
Simulation: Electronic
temperature
Simulation: Digital input
in simulation
Digital Input in Manual
mode
Simulation: Diagnosis
Note
The instrument status can be simulated using SIMATIC PDM. This allows you to test the
reaction of the automation system to errors.
68
Corrective action
Bring temperature of electronics module to within allowed
range
Either adjust diagnostic alarm limits or remove cause of
out of range sensor value
Perform calibration and timer will automatically be reset
Perform service and reset timer using SIMATIC PDM
Perform service on sensor or replace unit
Wait for sensor test to finish, then remove test magnet
from device housing
Device is defective; replace unit
Sensor is defective; replace sensor
To return to normal operation, disable the simulation with
SIMATIC PDM
To return to normal operation, disable the simulation with
SIMATIC PDM
To return to normal operation, disable the simulation with
SIMATIC PDM
To return to normal operation, disable the simulation with
SIMATIC PDM; reset the block mode of the Digital Input
Function Block
To return to normal operation, disable the simulation with
SIMATIC PDM
Pointek CLS200/CLS300 digital
Operating Instructions, 05/2021, A5E47904060-AA
Byte
Bit
0
0
2
3
4
5
6
2
6
7
3
1
2
3
4
5
6
7