– Press ⇑ or ⇓. The display switches to the current measured sensor value in counts.
– Press ⇑ or ⇓ to enter Edit Mode; the sensor value is frozen and ready for editing.
– Set the sensor value to approximately 1000 counts above the value of the current
– After editing the least significant digit (or leaving it unchanged), press ⇓ to terminate
– Press M to exit.
3. Adjust the Off to On switch point (Mode 25):
– Use the M button to navigate to Mode 25.
– Set the value to 55% as a starting point.
4. Adjust the On to Off switch point (Mode 26):
– Use the M button to navigate to Mode 26.
– Set the value to 45% as a starting point.
5. Adjust the other parameters of the device as desired.
Pointek CLS200/CLS300 digital
Operating Instructions, 05/2021, A5E47904060-AA
reading. Press ⇑ to edit the value of each digit, and press ⇓ to move the cursor to the
next digit.
the procedure and save the new value. The display now shows the new value for the
100% Application Range setting.
Note
A minimum hysteresis (difference between the Off to On switch point and the On to
Off switch point) of 10% must be maintained for reliable operation. In some situations,
it may be desirable to increase the hysteresis between the two switch points to prevent
false tripping (e.g. turbulence in the process).
7.3 CLS200 digital switching point setup