Local operation
7.2 Programming via the Local User Interface (LUI)
7.2.11

Mode 16: PROFIBUS Ident Number (default: 1)

Determines which of two device operating modes to select. Pointek CLS200/300 Digital
recognizes two operating modes in relation to the DP Master:
Mode Description
0
1
To set the device operating mode:
• Select Mode 16. The current device operating Mode (0 or 1) appears in the primary
reading field.
• Press ⇑ or ⇓ to select the desired operating mode.
• Press M to save the selection and exit.
Applies to PROFIBUS PA applications only. If in standalone application (no network), leave
1)
the node address at the default value.
7.2.12

Mode 19: 0% application range setting

This point corresponds to the left limit of the bar graph in the digital display.
CLS200 0% Application Range setting
To adjust the 0% Application Range setting for CLS200:
1. Install the device in the process.
2. Use the M button to navigate to Mode 19.
3. Set up the process to provide the recommended condition for your process from the table
below:
Application
General
Demanding
Interface
detection
4. Press ⇑ or ⇓. The display switches to the current measured sensor value in counts. Record
the count value.
5. Press ⇑ or ⇓ to enter Edit Mode; the sensor value is frozen and ready for editing.
6. Set the sensor value to approximately 300 counts below the value obtained in step 4. Press
⇑ to edit the value of each digit, and press ⇓ to move the cursor to the next digit.
46
Conforms to profile version 3.0 Class
B device with no extensions.
Conforms to profile version 3.0 Class
B device with extensions.
Material
dry solids
low viscosity liquids
hygroscopic / wet solids
high viscosity and high conductivity
liquids
liquid A / liquid B
foam / liquid
Generic: can substitute transmitters conforming to
PROFIBUS PA profile 3.0, one Discrete Input Function
Block.
Device-Specific: full functional range of Pointek
CLS200/300 with Discrete Input Function Block.
Setup conditions
sensor uncovered;
min. 100 mm (4") free space all around
sensor immersed then uncovered; but
retaining max. possible material
buildup
sensor immersed in the material with
the lowest dielectric constant
Operating Instructions, 05/2021, A5E47904060-AA
Pointek CLS200/CLS300 digital