Technical data
11.1 Pointek CLS200/300
Enclosure
Termination
Construction
Optional thermal
isolator
Cable entry
Ingress protection
Separation between
Zone 0 and Zone 1
(ATEX II 1/2G)
Or 1.4404 material.
1)
Note
The use of approved watertight conduit hubs/glands is required for Type 4/IP65 or IP68
(outdoor applications). For CE requirements the use of EMC rated cable entries is required for
all CLS200 devices.
Weight
Weight varies based on configuration. For example:
compact Pointek CLS200, 100 mm (4") insertion
length, ¾" process connection
84
removable terminal block, 2.5 mm2 max.
Tightening torque of terminal screws: 0.5 to 0.6 Nm
Conductor cross section:
1 conductor
solid: 0.2 to 2.5 mm
2
flexible: 0.2 to 2.5 mm
flexible, with ferrule with or
without plastic sleeve: 0.25 to
2.5 mm
2
AWG 24 to 12
powder-coated aluminum with gasket
316L
stainless steel
1)
2 x M20 thread
With ATEX approval:
Default: 2x M20x1.5
With selection of option Pos. 33a: 2x NPT 1/2" tapered ANSI B1.20.1
Type 4 / IP65 standard, IP68 optional (depending on cable entry option)
Note: the use of approved watertight conduit hubs/glands is required for Type
4/IP65 or IP68 (outdoor applications).
Material of the separation element (partition wall)
Stainless steel, 1.4404 (316L)
Glass, Inconel 600 (Glass seal)
2 conductors with same cross section
solid: 0.2 to 1.0 mm
stranded: 0.2 to 1.5 mm
2
stranded, with ferrule without plas-
tic sleeve: 0.25 to 1.0 mm
stranded, TWIN ferrule with plastic
sleeve: 0.5 to 1.0 mm
1 kg (2.20 lb.) approx.
Operating Instructions, 05/2021, A5E47904060-AA