Siemens Pointek CLS200 Operating Instructions Manual page 40

Hide thumbs Also See for Pointek CLS200:
Table of Contents

Advertisement

Local operation
7.2 Programming via the Local User Interface (LUI)
Function
Mode
#
M
Display Source 13
*
Unit
14
*
Node address
15
(PROFIBUS
only)
PROFIBUS
16
Ident Number
Application
19
Range, Lower
Limit / 0%
Application
20
Range, Upper
Limit / 100%
Alarm output
23
*
trigger
Contact type
24
*
Switch Point 1
25
(Rising Edge)
OFF to ON
Switch Point 2
26
(Falling Edge)
ON to OFF
Local Status
27
*
Text
In Modes indicated by an asterisk (*), press M to store a selection. In other Modes, press to store numerical values.
1)
If L appears in the Mode indicator field of the display, the HW Write Protection is activated.
2)
If LA, LL, Lc or Li appears in the Mode indicator field of the display after releasing the HW Write Protection, there is an
3)
additional block on local operation via the bus. Lock, explains how to release this using SIMATIC PDM. In measuring
mode, if neither L, LA, LL, Lc or Li, appears in the Mode indicator display field, local operation is possible.
40
Key function
1)
Scroll up or down to select an option.
Scroll up or down to select an option.
Enable Edit func-
Move cursor to the
tion, or incre-
right, or store edit-
ment digit.
ed value.
Scroll up or down to select an option.
Enable Edit func-
Move cursor to the
tion, or incre-
right, or store edit-
ment digit.
ed value.
Enable Edit func-
Move cursor to the
tion, or incre-
right, or store edit-
ment digit.
ed value.
Scroll up or down to select an option.
Scroll up or down to select an option.
Enable Edit func-
Move cursor to the
tion, or incre-
right, or store edit-
ment digit.
ed value.
Enable Edit func-
Move cursor to the
tion, or incre-
right, or store edit-
ment digit.
ed value.
Scroll up or down to select an option.
Display, or explanation
⇑ and ⇓
Source of measured value: 0 = OUT (out-
put);
1 = PRIM (primary value);
2= SENS (sensor);
3 = TMP E (electronics temperature)
Select K, °C, °F, °R (if electronics temper-
ature selected in Mode 13).
Assign slave address on the PROFIBUS
network (0 to 126). Recommended set-
ting range 1 to 125.
Select device mode: 1 =according to
profile; or, 2 = according to profile with
full device specific support.
Adjust lower limit of application range.
Adjust upper limit of application range.
Select the source event to switch the
alarm output. See Mode 23: Alarm out-
put trigger (default: dIAG) (Page 49).
Set contact functionality in case of event:
(logical inversion of alarm output switch)
- Make contact (CLOSE)/ Break contact
(OPEn)
Set % of range at which switch will
change from OFF to ON.
Set % of range at which switch will
change from ON to OFF.
Select presentation of status text. See
Mode 27: Local Status Text (default:
U_075) (Page 52).