Mode 25: Switch Point Off to On/Switch Point 1/Rising Edge (default: 55%)

Note
Initial setup can be carried out prior to mounting into the process, but it is extremely
important to calibrate the unit and adjust the sensitivity on the product itself.
Allows you to adjust the switch behavior by setting the percentage of the Application Range
(defined in Mode 19 and Mode 20) at which point the logical switch will change from Off to
On.
This symbol appears to the left of the numerical value to indicate a Rising Edge value.
Switch Point 1 must have a value greater than or equal to the value for Switch Point 2. If you
enter a lower value, Switch Point 2 will be adjusted to the same value.
The permitted range is limited by the distance of the Switch Point to the next Measuring
Limit.
To view the current setting for Switch Point 1:
• Select Mode 25.
• The current setting appears in the primary reading field as a percent of the Application
range (0 to 100%).
• Press M to exit, or:
To adjust the setting:
• Press ⇑ or ⇓.
• The display switches to the current measured Sensor Value as a percent of the Application
Range (0 to 100%).
• Press ⇑ or ⇓ to open Edit mode: the Sensor value is frozen.
• Press ⇑ to edit the value of each digit, and press ⇓ to move the cursor to the next digit.
• After editing or leaving the least significant digit unchanged, press ⇓ to terminate
procedure and save the new value.
• You see the new setting for Switch Point 1.
• Repeat the process, or press M to exit.
Pointek CLS200/CLS300 digital
Operating Instructions, 05/2021, A5E47904060-AA
7.2 Programming via the Local User Interface (LUI)
Local operation
51